List of circuit breakes and outlets:
Local: C48-2 (Dipole station), marked as "A" on drawing
- 2 circuit breakes, 3 amperes MCB type C and 2 120 volts outlets
- 2 circuit breakes, 5 amperes and 2 120 volts outlets
- 1 outlet, 120 volts, 0.2 amperes (for Signal Conditioner)
- 1 outlet, 120 volts, 0.7 amperes (for Rack Monitor)
- 1 outlet, 120 volts, 10 amperes (for General use)
Local: C49 wall and Pit , marked as "B" and "C" on drawing
- 4 circuit breakes, 3 amperes MCB type C and 4 120 volts outlets
- 2 circuit breakes, 5 amperes and 2 120 volts outlets
- 1 outlet, 120 volts, 0.2 amperes (for Signal Conditioner)
- 1 outlet, 120 volts, 0.7 amperes (for Rack Monitor)
- 1 outlet, 120 volts, 10 amperes (for General use)
Local: D11 Pit and wall, marked as "D" and "E" on drawing
- 4 circuit breakes, 3 amperes MCB type C and 4 120 volts outlets
- 2 circuit breakes, 5 amperes and 2 120 volts outlets
- 1 outlet, 120 volts, 0.2 amperes (for Signal Conditioner)
- 1 outlet, 120 volts, 0.7 amperes (for Rack Monitor)
- 1 outlet, 120 volts, 10 amperes (for General use)
Cable trays:
C side:
From C48-2 (2228" Tev D0 dipole station) to the first Quad station at C49 (1292" Tev D0). Length = 78 Ft. Width = 4" min.
From the first Quad station (1292" Tev D0) to the second Quad station at C49 (929" Tev D0). Length = 30 Ft. Width = 8" min.
From the second Quad station (929" Tev D0) to collision wall shield 390" Tev D0). Length = 45 Ft. Width = 12".
D side:
From the first Quad station to the second Quad station at D11. Length = 30 Ft. Width = 8" min.
From the second Quad station to collision wall shield. Length = 45 Ft. Width = 12".