RACK MONITOR CONFIGURATION
9 Rack Monitors are installed in the Tunnel :
4 in the Proton Side (CTL_RM_02-11 to CTL_RM_02-14) ;
5 in the Anit-Proton Side (CTL_RM_02-01 to CTL_RM_02-05).
The configuration of the rack monitors are identical :
P3 as Output : RMI Reset and Amplifier Crate Control ;
P2 and P8 as Ouput for the pot motion ;
P7 as Input : Alarms and status of motors, Smoke Detector Alarm and Emergency Line ;
P10 (pin 1 to 4) : LVDT values.
The variable BMASK represents the switches configuration in front of the Rack Monitor panel. Actually, we have 3 Ouputs and 1 Input so the BMASK value is 0x07.
The Rack Monitors (CTL_RM_02-01 and CTL_RM_02-03) are not yet installed in the tunnel. They're used in the small control room for tests.
|
Name |
Location |
Configuration |
BMASK |
||||
|
P3 (Output) |
P8 (Output) |
P2 (Output) |
P7 (Input) |
P10 (LVDTs informations) |
|||
|
CTL_RM_02-01 |
A1 |
Not used |
A1-Up Control |
A1-Down Control |
Pin 1 to 7 : A1-Down Status |
Pin 1 : A1-Up Position |
0x07 |
|
Pin 2 : A1-Down Position |
|||||||
|
Pin 9 to 15 : A1-Up Status |
Pin 3 : A1-Out Position |
||||||
|
Pin 4 : A1-In Position |
|||||||
|
CTL_RM_02-02 |
A1 |
Pin 1 : RMI reset |
A1-In Control |
A1-Out Control |
Pin 1 to 7 : A1-In Status |
Not used |
0x07 |
|
Pin 5 : Amplifier Crate Control |
Pin 9 to 15 : A1-Out Status |
||||||
|
Pin 16 : Smoke Detector Status |
|||||||
|
CTL_RM_02-03 |
A2 |
Not used |
A2-Up Control |
A2-Down Control |
Pin 1 to 7 : A2-Down Status |
Pin 1 : A2-Up Position |
0x07 |
|
Pin 2 : A2-Down Position |
|||||||
|
Pin 9 to 15 : A2-Up Status |
Pin 3 : A2-Out Position |
||||||
|
Pin 4 : A2-In Position |
|||||||
|
CTL_RM_02-04 |
A2 |
Pin 1 : RMI Reset |
A2-In Control |
A2-Out Control |
Pin 1 to 7 : A2-In Status |
Not used |
0x07 |
|
Pin 5 : Amplifier Crate Control |
Pin 9 to 15 : A2 -Out Status |
||||||
|
Pin 16 : Smoke Detector Status |
|||||||
|
CTL_RM_02-05 |
D1 - D2 |
Pin 1 : RMI Reset |
D2 Control |
D1 Control |
Pin 1 to 7 : D2 Status |
Pin 1 : D1 Position |
0x07 |
|
Pin 5 : Amplifier Crate Control |
Pin 8 : Emergency Line Status |
||||||
|
Pin 9 to 15 : D1 Status |
Pin 2 : D2 Position |
||||||
|
Pin 16 : Smoke Detector Status |
|||||||
|
CTL_RM_02-11 |
P1 |
Not used |
P1-Up Control |
P1-Down Control |
Pin 1 to 7 : P1-Up Status |
Pin 1 : P1-Up Position |
0x07 |
|
Pin 2 : P1-Down Position |
|||||||
|
Pin 9 to 15 : P1-Down Status |
Pin 3 : P1-Out Position |
||||||
|
Pin 4 : P1-In Position |
|||||||
|
CTL_RM _02-12 |
P1 |
Pin 1 : RMI Reset |
P1-In Control |
P1-Out Control |
Pin 1 to 7 : P1-In Status |
Not Used |
0x07 |
|
Pin 5 : Amplifier Crate Control |
Pin 9 to 15 : P1-Out Status |
||||||
|
Pin 16 : Smoke Detector Status |
|||||||
|
CTL_RM_02-13 |
P2 |
Not Used |
P2-Up Control |
P2-Down Control |
Pin 1 to 7 : P2-Up Status |
Pin 1 : P2-Up Position |
0x07 |
|
Pin 2 : P2-Down Position |
|||||||
|
Pin 9 to 15 : P2-Down Status |
Pin 3 : P2-Out Position |
||||||
|
Pin 4 : P2-In Position |
|||||||
|
CTL_RM_02-14 |
P2 |
Pin 1 : RMI Reset |
P2-In Control |
P2-Out Control |
Pin 1 to 7 : P2-Out Status |
Not Used |
0x07 |
|
Pin 5 : Amplifier Crate Control |
Pin 8 : Emergency Line Status |
||||||
|
Pin 9 to 15 : P2-In Status |
|||||||
|
Pin 16 : Smoke Detector Status |
|||||||
CONNECTED & TESTED CONNECTED BUT NOT TESTED NOT CONNECTED