DØ Control Room Procedures  

Please send comments to the DØ Run Coordinator
Last modified: Tue Oct 24 11:08:05 CDT 2006

D0 Run Plan Rescraping BLS Power Supplies Calorimeter for Non-CAL Shifters CFT Shifter On-Call CFT Operations Changing Prescales Controlled Accesses
Combined Test Stand Operations Disable/Enable Muon Front-End FPD Operations FPD Procedures for Non-Experts Halo Rates D0 High Voltage L1CTT Inputs to L1 Muon
Luminosity Magnet Operations Muon Shifter On-Call Power Outage Recovery Recovery from Online Database Disruption Resetting the NIKHEF Hall Probes Resetting Trips Due to Water Drip Detection SCL Inits
SMT Voltage Standard Acnet Plots STT Operations TLD Badges Training

Standard Run Procedures

The default running condition for a store - unless otherwise specified and approved by the Run Coordinator - is to run with all available readout crates in the global run with Recording On. Please review the D0 Run Plan for current plans and situations.Shift Captains are responsible for enforcing the Run Plan and resolving conflicts.

During colliding beam: Each detector shifter will communicate with the Shift Captain and DAQ shifter whether or not the crates should be included in the primary global run. Removal of any crates from the global run for reasons other then fixing immediate hardware or software problems must be approved by the the appropriate detector expert. Unless explicitly approved, the default condition is to leave the crates in the global run.

Work that influences or impacts the DAQ between stores must be scheduled in advance and approved by the Run Coordinator.

See the sections on CFT Operations & L1CTT Inputs to L1 Muon & Combined Test Stand Operations & STT Operations for special instructions.

Procedure in the case of rescraping and beam loss tuning by MCR   last updated 10 August 2006

  1. To tune losses for CDF, MCR usually does one or more of the following:
    • Change tunes and chromaticities
    • Move indidividual collimators, typically E03 (H&V) and/or D173 (H&V)
    • Clean the abort gap using the TEL.
    This should not have any impact on D0 data taking. If MCR calls and announces one of the above, keep taking data with SMT and Muon HV up. Watch our halo rates carefully until MCR has finished.
  2. If MCR announces a full rescrape, end the run, end the store, and put the detector to standby. Begin with the same store number again once the recraping is completed. This is the usual rescraping procedure as before. In particular, the DAQ shifter should issue corresponding store_end and store_begin commands; for the luminosity accounting it is perfectly OK to fragment a single store into separate time periods.
  3. If MCR announces anything not falling into the above two categories, remember that protecting the detector has priority. Put SMT & Muon to standby if in doubt, and/or call the run coordinator.
  4. FPD: as a basic (new) rule, the FPD will stay ON when SMT and Muons stay on. Refer to the FPD instructions for details, or ask an FPD on-call person.

CFT Operations   last updated 1 August 2003

When there is no colliding beam, the CFT crates are under the control of the CFT shifter.

STT Operations   last updated 16 August 2005

The 6 STT crates (x70-x75) are regularly part of the global run. These crates get inputs from the CTT and SMT and are monitored by the SMT shifter. In case of problems that cannot be solved by the SMT shifter, the STT primary (and then secondary) experts should be paged. The pager numbers along with phone numbers are posted at the SMT/STT console and on the STT Operations web-page.

In case of questions, please contact Junjie Zhu, x4097 (junjie@fnal.gov).

Magnet Operations   last updated 3 August 2005 (WML)

When necessary the Shift Captain is responsible for providing the D0 Ops Shifter with instructions on turning the D0 magnets ON/OFF or changing the polarities. The solenoid takes about 20 minutes to discharge and the toroid about 10 minutes. The shift captain should verify with the Ops Shifter that the magnet power supplies are locked out after being ramped down. Before the solenoid or toroid are turned on or off, MCR must be notified.

During shot setup, while following the Store Checklist, the Shift Captain will check that the magnets are ON, at full current and at the correct polarity as defined in the Run Plan. The Solenoid and Toroid Power Supply displays can be found on the Ops Shifter console between the CFT and SMT Shifter consoles.

Read the current at the magnet, not at the power supply and check the polarity of both Solenoid and Toroid in the Rev. Switch box.

Any changes in magnet currents should occur when there is no store in the Tevatron. Ask the Run Coordinator before any change. The MCR should be notified by the Shift Captain at least 10 minutes before any changes to the D0 magnet operating conditions.

The magnet polarity set will be changed twice per month. The solenoid polarity will flip once per month normally in the first week of the month, but this flip may be advanced or delayed by a week if there is some other impending need to power down the solenoid. The toroid may change with the solenoid and will change in the middle of the month. Future polarity sequences (R - Reverse, F - Forward) are given in the following table:
Date changed  4/8 4/24 5/5 5/15 6/3 6/22 7/6 7/21 8/3 8/23 8/31 9/18 10/6 10/22 10/27 11/15 1/3 2/2 2/17 2/23 6/9 6/22 7/6 7/21 8/5 8/24 9/8 9/26 10/23
Solenoid
Toroid
# days 16  11  10  19  19  14  15  13  20  19  17  16  19  26  30  15  13  14  15  15  19  15  18  14 

Special modes of operation for the magnets (no field for detector studies, etc.) will be described on a case by case basis in the run plan. As soon as such studies are over, we should return to the sequence outlined above.

In order to reduce operating expenses, the toroid should be powered OFF if it is known that collisions are not expected within the next 24 hours. Do not ramp down the solenoid. The toroid should be turned ON at least 1 hour before the expected shot setup.

During magnet current changes, follow the procedures outlined in the run plan for operating the luminosity counters' high voltage. If the solonoid polarity changes, the SMT shifter should be told in order to download new Lookup tables to the STT. No other detectors are known to be affected by the magnetic field changes.

D0 High Voltage   last updated 11 August 2006

Shift Captains are responsible for communicating to all detector shifters about the beginning of a store. The Shift Captain should specifically instruct the Muon & SMT detector shifters to set their HV to 100%. Data taking should be started after HV is at 100% for all detectors in trigger/readout.

The MCR should call D0 about planned store terminations. Near the end of a store, the Shift Captain will instruct the DAQ Shifter to end global data taking, followed by asking the Muon and SMT detector shifters to set their detector HV to "Standby". To avoid confusion, refer to the table below for which systems need to regulate their HV depending on beam conditions.

The Luminosity HV stays ON at all times, even during beam studies, but the setting of the HV to lower or higher percentages depends on the solenoidal field being off or on, as well as to the store state. It is the captains responsibility to change the Luminosity HV based on the solenoidal field, comics will automatically ramp for changes in store.

Beam conditions
  Detector    Shifter     Collisions    Injection     Beam studies    No Beam  
(Calibrations)
SMTSMT shifter 100% OFF OFF 100%
CALCAL shifter 100% at all times
ICDCAL shifter 100% at all times
MUONMUON shifter 100% Standby Standby Standby
LUM Captain 70% when solenoid off, or when there is not a store declared.
100% when solenoid on and in a store

Forward Proton Detector Operations   last updated 3 May 2005

For more details and default positions, read the FPD Run Plan.

The D0 Roman pots will be moved into position at the request of the the FPD experts. The Shift Captain must notify MCR and CDF before any pot is moved. The pots will remain at these positions for most of the store. The pots are retracted prior to the beam being aborted or machine studies. An FPD Expert will be present for all pot insertion.

The D0 FPD information is contained on ACNET page C72.

  • Subpage 1 shows if the home limit switch is set. When the system is in standby, these should all be 1.
  • Subpage 2 shows the Linear Variable Differential Transformer (LVDT) values. When the system is in standby, these should all be fluctuating around 0. As the pots are inserted, the fluctuations become small allowing precision of at least 0.2mm.
  • Subpage 4 shows the single counting rates for each pot that is instrumented with a trigger PMT. It also shows the losses for D0 and CDF at the bottom.

The D0 Roman pot operating positions are determined by one of two things, whichever occurs first. If the singles rate at a location increases much beyond 350kHz we stop there. Otherwise, we only insert until a 50% increase in proton losses at D0 (cumulative for all inserted pots) or a 50% increase in antiproton losses at D0 (cumulative for all inserted pots) as long as these both remain below 10 kHz and 6kHz respectively it remains. In addition we stop inserting if CDF antiproton halo increases by more than a factor 2 (cumulative for all pots). The Shift Captain can monitor D0 losses at C:D0PHTL and C:D0AHTL.

A-side pots affect p-halo and P-side pots affect a-halo. (Dipole pots don't affect halo up to nominal positions).

For reference, CDF also inserts Roman Pots during stores but they should have no effect on D0. CDF has an ACNET page for monitoring the pots at S4 subpage 4. In the middle of the page, the three readouts of the Tokyo Pot LVDTs is displayed (C:TPOT1M, C:TPOT2M, C:TPOT3M). Normal CDF LVDT readings when CDF pots are in their home position are approximately ~-890mils for pot1, -894mils for pot2 and -872mils for pot3.

FPD Procedures for Non-Experts   last updated 6 May 2005

Full details on FPD Procedures for Non-Experts and Emergency Pot Removal.

FPD Expert pager numbers are posted at the FPD console.

To assist in the 24/7 operations of the Forward Proton Detector & collection of the FPD data, the Shift Captains are trained and have been approved to perform many of the FPD tasks when an FPD Expert is not in the control room. There will be an FPD Expert on-call for day (08:00-20:00) and night (20:00-08:00) shifts to help resolve any problems.

The FPD Expert will insert the pots and verify that everything is in working condition (FPDGui, DAQ, HV, alarms). They will record initial conditions in the e-log, and review instructions with the Shift Captain.

The Shift Captain tasks are:

  • Contact the on-call expert 2 hours after a store is declared or luminosity is below 45e30, whichever is later.
  • Contact FPD expert if store conditions drastically change while the pots are in.
  • To collect data and monitor rates
  • Watch for SES alarms
  • Ramp down MAPMT voltages in case of a minor re-scrape (and ramp back to operating value -940V) afterwards or ramp down all FPD voltages in the case of a major rescrape (and contact expert to be available to ramp voltages back up afterwards)
  • Watch for fire alarms (occasional spurious alarms)
  • Follow the written FPD Pot insertion checklist to put the FPD system into standby at the end of the store or if the store ends unexpectedly (for example: quench). The green section of the checklist contains more detailed instructions for putting MAPMT HV to standby, retracting pots, putting trigger HV to standby and turning off control lines.

The Shift Captain must make sure the FPD system is in standby before the store ends. If anything happens that is not covered in these instructions, contact the on-call FPD Expert at any time. IF IN DOUBT, TAKE THE POTS OUT.

Emergency Removal (if system unresponsive):

If the computer stops responding to the mouse or the FPDGui becomes unresponsive contact the FPD Expert to bring back up the system. If you have to remove pots while the system is in an unresponsive state, then use the Emergency line to remove the pots. Verify the pots are at home in the C72 window (window 3 of ACNET display). Click in the upper right corner where you see -<4>+ on the - until you see -<1>+. On this page all of the pots should show a value of 1 if they are home. If you click on the + you will go to -<2>+ where you should see values hovering around 0. When the pots are home, turn the Emergency Line off. To put the FPD HV on standby, open an xterm from the Calorimeter console, and then do the the following:

  • Type setup d0online
  • connect to d0ol49 as d0fpd
  • Type /online/config/fpd/hv/fpd.hv &
  • Follow normal instruction for putting HV into standby
  • Close the HV Gui by clicking on File then Exit

Halo Rates   last updated 1 February 2006

Having the luminosity at 70% prior to declaring the store will keep the halo rates at a lower than normal value until the store is declared. You will need to know what halo values are acceptable while the luminosity system is at 70% in order to declare a store. At the moment, we are still investigating the optimum maximum values, so these numbers are somewhat arbitrary. In order to declare a store, the proton halo rate should be below 8 kHz and the antiproton halo rate should be below 4 kHz.

Luminosity   last updated 1 February 2006

During magnet current changes, follow the procedures outlined in the Run Plan for operating the luminosity counters' high voltage.

How to tell if the Luminosity information is updating in ACNET

Comments on the lmCaptain/lmShifter GUIs:

  • lmOnline acquires information from COOR and DataLogger. The COOR record should only update when there is an end run; the DL record should update whenever a new partition is written to disk. If there is no recorded activity, then the lmOnline keys can become very late. That is one reason why they never turn red in the GUI.
  • The lmACNETGW process is not critical. If the timestamp is stale, send email to d0luminosity@fnal.gov.
  • The L3SR and L3SRRATE applications usually require a reset of the server that sends L3 information to the Luminosity DAQ and DAQ_Monitor. Since it isn't a Luminosity DAQ application, the Lumi expert should not be called. It is a standard procedure for the DAQ shifters to restart the server; it fails quite often.
    • setup d0online
    • stop_daq l3fserver
    • start_daq l3fserver

Controlled Accesses   last updated 22 March 2005

Controlled accesses are often made available during unscheduled Tevatron down time - quench, power glitch, vaccum failure - which could happen 24/7. It requires significant coordination and cooperation between MCR and D0, and between the Run Coordinator, Shift Captain, Controlled Access Coordinator and Detector Experts. A maximum of eight people are allowed inside the D0 Collision Hall at one time during a controlled access. Each access is restricted to a maximum of four hours, although most are less than an hour. In order to take full advantage of an access opportunity, we need to be prepared and organized. If you have a job that can be done during a Controlled Access, then send email to the D0 Run Coordinator with:

  • a brief description of job,
  • the level of urgency,
  • the amount of time needed to complete the job, and
  • the persons who will perform the job.
With approval from the Run Coordinator, make a note on the Controlled Access whiteboard in the D0 Control Room, with your contact info & availability.

The Shift Captain should contact the MCR at the beginning of each shift, and as needed, to keep up with the dynamic schedule of the accelerator. D0 may be able to take advantage of unscheduled downtime to make a controlled access. Contact the D0 Run Coordinator for approval if there is an access opportunity. The list of Controlled Access Coordinators with their contact information is in the General Personnel Call Lists binder.

Your training must be current in order to enter the collision hall during accesses. See the section on Training for more details. Contact Eric McHugh or the D0 Run Coordinator if there are problems.

A Controlled Access must be performed by a team. A team goes into the collision hall and a team comes out from the collision hall. A single person can not be left in the collision hall for safety reasons.

TLD badges and hard hats must be worn in the collision hall. A rate meter is also required for each location. Sandals and open-toe shoes are not appropriate footwear because of safety concerns. Leather gloves and safety glasses may be required for some jobs.

Controlled Accesses - which we need in order to make periodic repairs and upgrades to our detector - are a privilege, not a right, extended to D0 by the Beams Division. Please be prepared, attentive and safe!

Training   last updated 17 February 2006

All shifters are required to have D0 Hazard Awareness Training [valid for 2 years] and Lock-Out Tag-Out (LOTO) I Training [valid for 100 years]. LOTO1 is being replaced by Electrical Safety Orientation, so either of these are valid.

Verify your training at the ES&H Training Plans page [FNAL domain]. Enter your ID (employee or visitor) and select ITH (Individual Training History) under Option 1. The Due Date shows when your training will expire or has expired. To renew your training, simply enroll yourself in a class or challenge exam session which are usually offered weekly.

D0 Hazard Awareness handouts & quizzes are available on the web. Copies are in the rack near the MCH1 door. Keep the handout, but return the quiz and the form on the last page to the appropriate slot in the rack. To renew D0 Hazard Awareness, you can also take the online quiz available here.

Send email to Eric McHugh to arrange LOTO I training.

Access to the D0 collision hall will either be Supervised or Controlled. To make any access, Radiological Worker Training [valid for 2 years] is required. Additional training - Fermilab Controlled Access Training [valid for 1 year] - is required in order to make a controlled access. It is strongly recommended that shifters get Rad Worker and Controlled Access training, and keep current, so D0 can take full advantage of all opportunites to access the detector for repairs, maintenance and upgrades.

TLD Badges   last updated 22 March 2005

Please read the Information for Temporary Badge Holders document (copies are also available in the control room), before asking the Shift Captain or Controlled Access Coordinator for a temporary TLD (thermoluminescent dosimeter) badge - they are the only ones authorized to distribute the temporary TLD badges! Please follow the Instructions for Issuing a Temporary TLD Badge. The web page for issuing Temporary TLD Badges can be found here.

Temporary TLD badges should be dropped in the box when:

  • the user has completed the one time access to the D0 Collision Hall, or
  • the user will not be entering a Radiation Area in the near future, or
  • the 3 month period (quarter) has ended.

If you will be at D0 for an extended period of time, and expect to enter Radiation Areas such as the D0 Collision Hall, you should fill out the permanent TLD badge form in the control room and leave the completed form in the box near the MCH1 door. Or, one can print the Permanent Badge Service Request Form from the web, and send to Dosimetry at MS119. The permanent badges (black plastic) are stored on racks near the DAB1 elevators. Every three months, the permanent badges are collected for testing and replaced with a new one. You will receive an email reminder at the end of each quarter to return your badge to the rack.

Please do not take your TLD badge off-site. The TLD badges (permanent and temporary) are used to measure the radiation exposure you receive while in Radiation Areas at Fermilab. It is a good habit to leave your TLD badge on the racks next to the elevator before you leave DAB1.

Temporary TLD badges & Permanent TLD request forms will be collected weekly and shipped to Dosimetry at MS119.

Power Outage Recovery   last updated 3 December 2002

In the event of an unscheduled power outage or interruption, please follow these procedures:

  1. DAQ, Ops and detector shifters have instructions on how to bring their systems back after a power outage. The Shift Captain should monitor their progress and help with the paging or calling of appropriate experts.
  2. Groups which want their on-call experts paged by the Shift Captain are:
    • CFT+PS
    • Luminosity
    • L1 Muon
    • FPD
    • L2
    • Online (Stu Fuess)
    • Rich Smith - restart the Hall monitors for the D0 solenoid
  3. Run Coordinator should be paged as well
  4. Other experts should to be paged or called in the case of problems only

Recovery from Online Database disruption   last updated 23 May 2005

After completion of any work on online database, or after any disruption in the work of online database, ask CFT Shifter to restart cft_gui.

SMT Voltage   last updated 13 August 2002

The SMT system is the only sub-detector in which damage can occur from high voltage (HV) being ON during beam losses. In the Calorimeter, ICD, Muon and Luminosity systesm - while the HV channels could trip - this will NOT damage the detectors.

The SMT shifter should not leave the control room for long periods of time (>10 minutes) while even the LV is up, especially not when the HV is up, unless there is another SMT shifter or expert to relieve him/her.

The Shift Captain MUST check with the SMT shifter that the SMT HV (and low voltage) is OFF before excusing him/her from the control room shift. The SMT shifter must also contact the SMT On-Call expert before leaving.

We require Shift Captains to be around during all shifts with beam (even if there are no collisions) due to a single reason - SMT radiation protection.

Combined Test Stand (CTS) Operations   last updated 4 February 2003

The Combined Test Stand (CTS) resides on the third floor of DAB, and is used to test AFEs, sequencers, sequencer controllers and the CTT.

The CTS runs can continue to be performed as SDAQ runs on an as needed basis. The person operating the CTS is required to keep the CFT+PS Shifter informed of CTS activities and the DAQ Shifter of CTS runs.

The CTS runs should have prescales set to provide L1 trigger rates of less than 50 Hz. If higher trigger rates are required, such studies should be performed between stores, and only after notifying the Shift Captain and DAQ Shifter.

Sometimes, crate x9 shows up at the DAQ Console as 100% L1 FEB, but this has no impact on the data taking, and can be ignored.

Changing Prescales   last updated 20 July 2004

There are many factors which affect the optimization of prescale sets for global running: trigger and DAQ rate capabilities, off-line farm production status, physics goals of the experiment, etc. Trigger Meisters with guidance from Trigger Board are creating/optimizing prescale sets. The current trigger list and prescales can be found in the Run Plan. We have run durations optimized for the for the instantaneous luminosity profile in a store. The run duration limits can also be found in the Run Plan.

For global runs, the rate to tape is not a measure of the D0 efficiency. It could be that we are limited by L1 or L2 rates, rather then rate to tape. It is the Trigger Meisters who optimize all rates. Do always use the prescale sets as per Run Plan. In the case of serious problems with some of the rates you should page Trigger Meisters, rather then try to modify prescales or use higher/lower prescale files. They will help you to resolve problems, if any, or will make long term changes in the prescale files.

BLS Power Supplies   last updated 7 November 2002

Rick Hance and Mike Cherry have prepared a safety document which details the Procedures for Changing a Calorimeter BLS Power Supply.

This procedure is for those times when Electrical/Electronics Operations personnel are not available - such as at short controlled accesses during off-hours. The urgency of replacing a BLS power supply will be determined by Nirmalya Parua (or by the Calorimeter Expert on-call when Nirmalya is away). Spare power supplies are located at the NE and SW corners of the D0 Collision Hall.

The procedure requires two physically fit, strong and healthy helpers to maneuver the heavy (50 kg) power supplies. One of the helpers should always be the Operations Tech on duty who is familar with the process. Nirmalya has provided a List of Qualified Helpers. The qualified helpers must wear leather gloves and steel-toed shoes during the maneuvering of the BLS power supply. The person(s) handling the water hoses must wear safety glasses.

If the bad BLS supply is on the north or south central platform, first notify the SMT shifter or expert to turn off their supplies (IB and sequencer). This is a preventative measure to protect against accidental power trips due to water leak detection.

Tools required: Flashlight; Phillips & Standard screwdriver; two disconnect fitting plugs for water hoses; bucket & box of Kimwipes.

L1CTT Inputs to L1 Muon   last updated 30 July 2003

If problems are noticed in L1Muon, ask both the CAL/Muon and CFT shifters to check their respective subsystem. The L1CTT sends track information to the L1Muon and therefore both systems are coupled.

CFT Shifter On-Call   last updated 1 August 2003

If any CFT major alarms occurs while the CFT shifter is on-call, summon the on-call shifter to the control room (consultation by phone is not sufficient) to address the issue. If for any reason the CFT shifter is unable to personally return to the control room within minutes, page the CFT on-call expert.

Muon Shifter On-Call   last updated 19 December 2003

In the case of long periods of no colliding beams, the Shift Captain might release the shifter responsible for the muon system (the CALMUON shifter) to on-call status. Before the shifter leaves the control room:

  1. Be sure that the HV on all muon detectors is set to Standby and locked. Document the HV status in the e-log.
  2. Check that there are no major muon alarms. Document this check in the e-log.
  3. Check that all muon crates can be readout in the zero bias run (unless specifically removed from the run by experts). Document this check in the e-log.
  4. Provide the Shift Captain with a phone number where you can be reached if there is a problem with the muon system during the remainder of your shift.

Calorimeter for Non-CAL Shifters   last updated 22 July 2002

Nirmalya Parua has written a four page PDF with basic calorimeter instructions for Shift Captains and DAQ Shifters for the times or shifts when there is no Calorimeter Shifter in the D0 Control Room. It is also available in [PPT].


There will be periods, particularly on owl shifts with no beam or chance of beam, when the Calorimeter Shifter is on-call and not in the Control Room. By default the Calorimeter crates are left in the global zero-bias run, but on occasion one of the CAL crates (x40-x4b) will assert 100% L1 FEB, such that data taking has stopped.

Solution:

  1. DAQ Shifter should pause the run
  2. Go to the CAL console, screen 1 (on right), Supply GUI, Mode Shift tab
  3. Click on 'Global T&C Reset'
  4. Click on 'Global ADC Reset'
  5. Click on 'Global T&C Reset' again
  6. DAQ Shifter should issue an SCLinit
  7. DAQ Shifter should resume run

If for some reason the 'Supply GUI' is not open, you can do:

setup d0online
/online/config/cal/supplies/supply_all &

in order to complete Step 2 above.

Issuing SCL Inits   last updated 12 January 2003

Only the DAQ Shifter should issue the manual SCL inits during global physics data taking:
  • To clear Muon Readout errors (PDT,MDT,etc.)
  • Before resuming a run after a Calorimeter ADC error
  • Before resuming a run after a CFT+PS download
  • To clear L1 CTT FEB (with approval from CFT shifter)
  • Before resuming a run after an SMT download
All shifters should clearly communicate requests for Pauses and SCL inits with the DAQ Shifter, and vice versa!

Resetting the NIKHEF Hall Probes   last updated 13 January 2004

Once an hour the NIKHEF hall probes between the CFT and the Solenoid and on the faces of the Central Calorimeter are read out and logged to the D0 online production database. On rare occasions the readout system crashes. Experience has shown that most often simply cycling the power to the hall probes enables the readout system to reawaken and proceed normally. The Shift Captain may be requested by a member of the Hall Probe team (Paul Balm, Pieter Houben, Rich Smith, Gene Fisk) to cycle the power to the hall probe system. This is accomplished by walking to rack M214 (2nd floor MCH, far end, N side), locating the lowest panel in the rack (gold anodized, labeled "Power Supply Nikhef Hall Probes"), noting a green LED and switch on the right end of the panel, moving the switch from "Bypass/On" to "Remote/Off", then verifying that the gray cable (emerging from the rack just above the panel) with metallic connector body is properly plugged into the port marked "Cannode 2" on the panel, waiting 15 seconds, then moving the switch handle to "Bypass/On" once again.

Resetting Trips Due To Water Drip Detection   last updated 22 January 2003

In many D0 systems, water is used to cool down the electronics. We do have a protection system which turns off water to the affected area(s) in the case of a water leak detection. This system works reliably - most of the alarms were caused by a real water leak. In the past we have had cases when the control room shifters were trying to reset water drip alarms multiple times without investigating the problem. As a result, every time the alarm was reset, water valves were opened and even more water leaked. Water can be very seriously damage the detectors and electronics.

Based on experience accumulated over the last 2 years of operations, we have developed rules for handling water related alarms. Please read and follow them from now on.

  1. The rules cover water drip and water flow trips both in MCH and in the D0 Collision Hall.
  2. In the case of a water related trip, the shifter responsible for the affected sub-system should NOT reset it, rather:
    • Call the Ops shifter who will document the trip in the logbook, check the level of the water in the cooling system and investigate reason(s) for the trip in the MCH or Collision Hall (if latter is accessible)
    • Inform detector group leader(s).
  3. If the leak is in the MCH, the Ops shifter will investigate the area affected and, if no water is found, could proceed with resetting the trip condition. If in the same area a trip will occur within 12 hours, the Ops shifter has to call the D0 Mechanical Operations Leader. Only after his/her approval and development of a specific plan of handling the situation should the trip be reset.
  4. If the leak is in the D0 Collision Hall and the hall is accessible (shutdown), the Ops shifter should proceed according to Item 3 above. If the hall is not accessible (collider operation), the detector group leader in consultation with the Ops shifter can instruct the detector shifter(s) to reset the trip. If a second trip occurs within 12 hours, the Run Coordinator has to approve further attempts to reset a trip after a detailed plan of handling each specific case is developed.

In summary: control room shifters should NOT reset water trips without consultation with both the Ops shifter and the detector group leader(s). If the same water trip repeats within less than 12 hours, the D0 Mechanical Operations Leaders and/or Run Coordinator must approve resetting a trip condition.

Disable/Enable Muon Front-End   last updated 16 July 2003

This message is just to serve as a quick reminder for muon shifters (and an update for Shift Captains/DAQ Shifters) on who you need to contact when you disable/enable a muon front end with the readout_client gui.

  1. If you have a problem with a front end, contact the subsystem expert before disabling the front end! It is the subsystem expert who should make the decision to disable (or enable) the front end.
  2. Once the decision has been made to disable the front end, the front end must also be disabled at level 1. You do not need to call the L1 Muon expert for this. You can disable the front end by running the l1muon_inputs.py gui (in /projects/l1muo/vme_gui).
    There is documentation on how to run the gui.
  3. The L2 input configuration file is automatically updated when the input is disabled in the muon GUI. To make the change active, the DAQ shifter should re-initialize COOR and then start the global run. At this point the input configuration in the L2 crate is updated. Starting the run will fail with a timeout while the SLIC cards in the L2 muon crates are downloading their new configuration. After this, the run can be started properly and the L2 dataflow GUI will show the corresponding SLIC input as a gray box. The L2 expert does not need to be contacted.

Standard Acnet Plots   last updated 24 October 2005

There are two sets of ACNET plots that captains should place in the logbook during their shift.

  1. If there is beam during the shift, ple3ase make a summary plot of the shift. This can be done a half hour before the end of the shift. From the 'D0 STORE II' page, plot D0PHTL, D0AHTL, and D0FLTL.
  2. If there is a shot setup during the shift, after things have calmed down, put the following three plots in the logbook:
    1. "SMT DOSE SUM" page. A good choice for the upper bound would be 50-100. Choose the time frame from when the rates started to rise to just after when the values were reset to zero.
    2. "SMT DOSE SEC" page. Here a good choice for the upper bound would be 0.5-1.0.
    3. "SMT DOSE MIN" page. If v:CLDRST does not work, just comment it out.

If you do not know how to put plots in the logbook, consult the vade mecum, or talk to another captain. Please make sure that you invert the image.